IEC 60502-1 / 60502-2  ·  SWA, Steel Wire & AWA Armoured Cable Manufacturer
ZMS Cable logo
Home / Products / Special Armoured Cables / Fire Resistant Armoured Cable
950 °C / 90 min · IEC 60331

Fire Resistant Armoured Cable

Mica-barrier fire resistant armoured cable, 950 °C for 90 minutes to IEC 60331, with LSZH sheath for life-safety circuits.

Rated voltage0.6/1 kV
ConductorClass 2 stranded copper
Fire barrierMica tape over each conductor
InsulationXLPE or LSZH
Product overview

Construction and performance

Fire resistant cable is specified for circuits that must keep working while the building is on fire: fire pumps, smoke extraction fans, lifts, emergency lighting and alarm sounders.

The fire resistance comes from a mica tape barrier wrapped directly over each conductor, backed by XLPE or LSZH insulation, a steel tape or wire armour and an LSZH oversheath. Tested to IEC 60331 at 950 °C for 90 minutes, with the water spray and mechanical shock variants available.

The LSZH sheath keeps smoke opacity and halogen content low, which is usually a separate requirement in the same specification.

Key properties

  • Circuit integrity 950 °C / 90 min
  • LSZH sheath, low smoke and halogen
  • Armour retains mechanical protection during evacuation
  • CWZ and water spray options

Technical data

PropertySpecification
Rated voltage0.6/1 kV
ConductorClass 2 stranded copper
Fire barrierMica tape over each conductor
InsulationXLPE or LSZH
ArmourGalvanised steel tape or wire
OversheathLSZH, low smoke
Fire testIEC 60331-21, 950 °C / 90 min
Optional testsBS 6387 CWZ, BS 8491, water spray
Smoke / halogenIEC 61034, IEC 60754
Cross-section1.5 – 240 mm²
StandardIEC 60502-1, BS 7846
Request a Quote
Standards & applications

Built to the standard the project specifies.

Test certificates and type test reports are supplied with the drum documents.

IEC

IEC 60331-21 — Compliance on request

BS

BS 6387 CWZCompliance on request

BS

BS 7846 — Compliance on request

IEC

IEC 61034 / 60754 — Compliance on request

Typical applications

  • Fire pump and sprinkler supplies
  • Smoke extraction and pressurisation fans
  • Emergency lighting and alarm circuits
  • Lift and evacuation systems
  • Tunnel and metro life-safety circuits
Engineering support

Need this cable sized for your route?

Send the laying method, soil conditions and quantity. We confirm armour, sheath and lead time in the quotation.

Request a quotation

Request this cable

Send cores, cross-section, voltage grade and quantity. We will confirm armour type, sheath and lead time.

By sending this form you agree to our privacy policy. We reply within one business day.