Corrosion Classes for Buried Armoured Cable
Galvanised steel tape is an excellent default and a poor choice in the wrong soil. The difference between a cable that lasts thirty years and one that fails in five is usually the sheath compound and the soil chemistry, not the armour thickness.
What attacks the armour
A buried armoured cable has two barriers: the oversheath and the armour. The oversheath keeps water and electrolytes away from the armour; the armour is the mechanical layer behind it. Corrosion begins at a breach — a manufacturing defect, a handling graze, a stone point-load during backfill — and progresses in the local environment created by that breach.
Four soil conditions matter most:
- Chlorides — coastal fill, saline groundwater, de-icing salt. Chloride destroys the protective zinc layer on galvanised steel quickly and then attacks the steel itself.
- Sulphates and low-resistivity soil — aggressive to zinc and to steel, and common in industrial and reclaimed land.
- Stray direct current — from traction systems, cathodic protection of nearby pipelines, or welding operations. Stray DC causes fast electrolytic corrosion of steel armour.
- Alternating current in the armour — on long single-core runs with steel armour, circulating currents both heat the cable and accelerate corrosion at any breach.
The three practical answers
1. Keep the steel, upgrade the sheath
For most aggressive soils the most economical reliable answer is a PE oversheath instead of PVC. PE has much lower water vapour permeability and better chemical resistance, and it is the standard choice for buried cables in coastal and industrial ground. The armour stays galvanised steel tape, which is mechanically appropriate for LV distribution. This is the construction usually described as heavy-duty corrosion-resistant armoured cable.
2. Change the armour metal
Aluminium wire armour is more resistant than galvanised steel in many soils and, being non-magnetic, it removes the circulating-current problem on single-core AC. It is not a universal answer — aluminium is amphoteric and suffers in strongly alkaline or acidic ground, and it is softer than steel where impact governs. Where it is used, the oversheath must still be specified for the soil.
3. Change the route or add cathodic protection
Where soil is exceptionally aggressive and the run is accessible, ducting the cable or rerouting around the contaminated zone is more reliable than any sheath. Cathodic protection is applied to buried steel structures rather than to cable armour, but it is relevant because a CP system on adjacent plant can create stray currents that attack the cable.
How to classify the route
Several national codes classify soil aggressiveness by resistivity, redox potential, pH, chloride and sulphate content, and produce a class from 1 (negligible) to 5 (very high). Where a project has a geotechnical report, use it: the classification is not a marketing term, it is a measurement. Where there is no report, the practical minimum is to state the environment — coastal, industrial, reclaimed, agricultural — and let the sheath be selected against it.
A specification that says only “armoured cable, PVC sheath” in a coastal industrial park is not a specification. It is a placeholder that will be filled in with the cheapest compliant item.
What we ask before quoting a corrosive route
- Soil or groundwater chemistry, if available; otherwise the site description and distance from the coast.
- Whether the cable is single-core or multi-core, and the formation.
- Whether the route crosses other buried services with cathodic protection.
- The design life expected of the installation.
Where the soil survey rules out galvanised steel altogether, the answer is a different armour rather than a thicker sheath: the corrosion resistant armoured cable is built for that case, and the AWA aluminium wire armoured cable removes the ferrous component entirely where the route is wet and saline.
Corrosion-resistant armoured cable