SWA vs Steel Wire vs AWA Armour: Which One for Your Route?
The armour is the part of the cable that decides whether it survives installation and service. The three armour types used for power and control cables — steel tape, steel wire and aluminium wire — resist different things, and choosing between them is a question about the route, not about price.
What each armour actually does
Steel tape armour (STA, usually sold as SWA in British practice) is a helix of galvanised steel tape applied over the bedding. It resists radial impact and compression: a digger bucket, a dropped kerbstone, the point load of backfill stone. It does not carry tensile load, and it offers no protection if the cable is pulled hard around a bend. It is the default answer for buried LV distribution, ducted and un-ducted, and for building incoming supplies.
Steel wire armour (SWA in the mechanical sense, common on MV) is a layer of galvanised steel wires laid helically. Because wires are continuous along the cable, the armour takes tensile load as well as impact. That makes it the choice where the cable is pulled, suspended, trailed, or exposed to repeated mechanical abuse — mine roadways, risers, river and bridge crossings, subsea landing approaches and heavy mobile equipment supply. It is also the normal construction for medium voltage, where the thicker insulation and larger conductor call for a higher mechanical duty.
Aluminium wire armour (AWA) looks identical to steel wire armour but is non-magnetic. It exists for one reason: on single-core AC cables, a magnetic steel armour surrounds the conductor with a closed ferromagnetic loop. The alternating flux induces eddy currents and hysteresis losses in the armour, heating it and reducing the current-carrying capacity of the cable. Aluminium wire is non-magnetic, so the effect is negligible. It is also lighter and more corrosion-resistant in some soils, but it is not a substitute for steel where tensile strength or impact resistance governs.
The three questions that decide it
1. Is the cable single-core AC?
If yes, steel armour of any kind is the wrong answer. Use aluminium wire armour, or use a non-armoured single-core cable inside a duct or tray. Single-core cables in trefoil or flat formation with steel armour will overheat and derate; no amount of oversizing fixes the physics.
2. Does the route put the cable in tension?
Long pulls, vertical risers, suspended spans, trailing cables on mobile plant and cables laid in moving ground all put the armour in tension. Tape armour has almost no tensile capability: it will open up at a joint or pull back from the termination. In those routes specify wire armour and state the expected pull and the maximum tension the drum can take.
3. What is the governing damage mechanism?
For buried LV distribution the governing risk is usually third-party damage during later excavation, and tape armour is the economical answer. For open yards, ports and mine roadways the governing risk is impact and abrasion, where wire armour is better. For chemical and saline environments the governing risk is corrosion of the armour itself, and the correct answer is often a PE sheath over galvanised steel rather than a change of armour metal — a subject for the corrosion note in this series.
Voltage ranges in normal use
- Steel tape armoured LV power — 0.6/1 kV, 1.5–400 mm², typically 1–5 cores. Direct burial, trenches, building incomers.
- Steel wire armoured MV power — 6/10 kV to 26/35 kV, 35–500 mm². Buried and exposed MV distribution, risers, crossings.
- Aluminium wire armoured single-core — 6–35 kV, 50–630 mm². Single-core AC feeders where steel would induce losses.
- Steel tape armoured control — 0.5–2.5 mm², 2–61 cores, usually with an overall screen.
What to write on the datasheet
A specification that says only “armoured” leaves the decision to the supplier. State the armour type, the material and the standard the armour is applied to: for example, “galvanised steel tape armour, double tape helix to BS 5467” or “galvanised steel wire armour, applied over bedding to IEC 60502-2”. Add the sheath compound and the expected installation method. That single line prevents the most common substitution in armoured cable supply — a lighter tape or a lower wire count that meets the drawing but not the duty.
Each armour type is a finished construction, not an option line. Steel tape belongs to the SWA armoured power cables used on buried LV routes; steel wire is the basis of the steel wire armoured MV cable where pulling tension matters; aluminium wire is the AWA armoured cable used where the armour must not form a magnetic circuit.